 Solid-state Multi-functional Timer
Timers 3. Output None: Relay output (DPDT) S: Transistor output (NPN/PNP universal use) E: Relay output (SPDT) with instantaneous relay output (SPDT) 4. Suffix 300: Dual mode models (signal ON/OFF-delay and one-shot) 301: Double time scale (range) models (0.1 s to 600 h)
H3CR-A
DIN 48 x 48-mm State-of-the-art Multifunctional Timer
* A wider power supply range reduces the number of timer models kept in stock. * A wide range of applications through six or four operating modes. * Reduced power consumption. (Except for H3CR-A8E) * Enables easy sequence checks through instantaneous outputs for a zero set value at any time range. * Length, when panel-mounted with a Socket, of 80 mm or less. * Time Setting Rings enable consistent settings and limit the setting range. * Panel Covers enable various panel designs. * PNP input models available. * Rich variety of inputs: Start, reset, and gate functions (11-pin models and -AP models)
Model Number Structure
I Model Number Legend
H3CR-A@@@-@
123 4
1. Number of Pins None: 11-pin models 8: 8-pin models 2. Input Type for 11-pin Models None: No-voltage input (NPN type) P: Voltage input (PNP type)
Solid-state Multi-functional Timer
H3CR-A
B-109
Ordering Information
I List of Models
11-pin Models
Output Contact Supply voltage 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC Transistor (Photocoupler) 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 0.05 s to 300 h H3CR-AS No-voltage input 0.1 s to 600 h H3CR-A-301 Voltage input Six multi-modes: A, B, B2, C, D, E H3CR-AP Dual-modes: G, J H3CR-A-300 Input type No-voltage input Time range 0.05 s to 300 h Operating mode (see note 2) Six multi-modes: A, B, B2, C, D, E Model H3CR-A
8-pin Models
Output Contact Supply voltage 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 100 to 240 VAC (50/60 Hz)/ 100 to 125 VDC 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC Transistor (Photocoupler) 24 to 48 VAC (50/60 Hz)/ 12 to 48 VDC 0.05 s to 300 h H3CR-A8S H3CR-A8E 0.1 s to 600 h Input type Time range Operating mode (see note 2) Four multi-modes: A, B2, E, J (Power supply start) Model H3CR-A8 No-input available 0.05 s to 300 h
H3CR-A8-301
Time-limit contact and 100 to 240 VAC (50/60 Hz)/ instantaneous contact 100 to 125 VDC 24 to 48 VDC/VAC (50/60 Hz)
Note: 1. Specify both the model number and supply voltage when ordering. Example: H3CR-A 100 to 240 VAC (50/60 Hz)/100 to 125 VDC Supply voltage 2. The operating modes are as follows A: ON-delay D: Signal OFF-delay B: Flicker OFF start E: Interval B2: Flicker ON start G: Signal ON/OFF-delay C: Signal ON/OFF-delay J: One-shot
B-110
Solid-state Multi-functional Timer H3CR-A
I Accessories (Order Separately)
Name/specifications Flush Mounting Adapter Y92F-30 Y92F-73 Y92F-74 Mounting Track 50 cm (l) x 7.3 mm (t) 1 m (l) x 7.3 mm (t) 1 m (l) x 16 mm (t) End Plate Spacer Protective Cover Track Mounting/ Front Connecting Socket 8-pin 8-pin, finger safe type 11-pin 11-pin, finger safe type Back Connecting Socket 8-pin 8-pin, finger safe type 11-pin 11-pin, finger safe type Time Setting Ring Panel Cover (see note 2) Setting a specific time Limiting the setting range Light gray (5Y7/1) Black (N1.5) Medium gray (5Y5/1) Hold-down Clip (see note 3) For PL08 and PL11 Sockets For PF085A Socket PFP-50N PFP-100N PFP-100N2 PFP-M PFP-S Y92A-48B P2CF-08 P2CF-08-E P2CF-11 P2CF-11-E P3G-08 P3G-08 with Y92A-48G (see note 1) P3GA-11 P3GA-11 with Y92A-48G (see note 1) Y92S-27 Y92S-28 Y92P-48GL Y92P-48GB Y92P-48GM Y92H-7 Y92H-8 Models Timers H3CR-A8E Relay output (SPDT) Relay output (SPDT)
Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket. 2. The Time Setting Ring and Panel Cover are sold together. 3. Hold-down Clips are sold in sets of two.
Specifications
I General
Item Operating mode H3CR-A/-AS H3CR-AP H3CR-A8/-A8S A: ON-delay B: Flicker OFF start B2: Flicker ON start C: Signal ON/OFF-delay D: Signal OFF-delay E: Interval G: Signal ON/OFF-delay (Only for H3CR-A-300) J: One-shot (Only for H3CR-A-300) 11-pin No-voltage input Voltage input H3CR-A/-A8/-AP:Relay output (DPDT) H3CR-AS/-A8S: Transistor output (NPN/PNP universal)* --DIN track mounting, surface mounting, and flush mounting UL508, CSA C22.2 No.14, NK, Lloyds Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1 for Timers with Contact Outputs. Output category according to EN60947-5-2 for Timers with Transistor Outputs. A: ON-delay (power supply start) B2: Flicker ON start (power supply start) E: Interval (power supply start) J: One-shot (power supply start)
Pin type Input type Time-limit output type Instantaneous output type Mounting method Approved standards
8-pin ---
*The internal circuits are optically isolated from the output. This enables universal application as NPN or PNP transistor.
Solid-state Multi-functional Timer
H3CR-A
B-111
I Time Ranges
Note: When the time setting knob is turned below "0" until the point where the time setting knob stops, the output will operate instantaneously at all time range settings.
Standard (0.05-s to 300-h) Models
Time unit Full scale set- 1.2 ting 3 12 30 0.05 to 1.2 0.3 to 3 1.2 to 12 3 to 30 s (sec) min (min) 0.12 to 1.2 h (hrs) 3 to 30 12 to 120 30 to 300 x10 h (10 h) 1.2 to 12
Double (0.1-s to 600-h) Models
Time unit Full scale set- 2.4 ting 6 24 60 0.1 to 2.4 0.6 to 6 2.4 to 24 6 to 60 s (sec) min (min) 0.24 to 2.4 h (hrs) 6 to 60 24 to 240 60 to 600 x10 h (10 h) 2.4 to 24
I Ratings
Rated supply voltage (see note 1) Operating voltage range Power reset Input 100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CRA8E) (see note 2) 85% to 110% of rated supply voltage (90% to 110% at 12 VDC) Minimum power-opening time: 0.1 s No-voltage Input ON impedance: 1 k max. ON residual voltage: 1 V max. OFF impedance: 100 k min. Voltage Input Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF Load connectable in parallel with inputs (terminals 6 and 7). * 100 to 240 VAC/100 to 125 VDC High (logic) level: 85 to 264 VAC/85 to 137.5 VDC Low (logic) level: 0 to 10 VAC/0 to 10 VDC * 24 to 48 VAC/12 to 48 VDC High (logic) level: 20.4 to 52.8 VAC/10.8 to 52.8 VDC Low (logic) level: 0 to 2.4 VAC/0 to 1.2 VDC H3CR-A/-A8 * 100 to 240 VAC/100 to 125 VDC (When at 240 VAC, 60 Hz) Relay ON: approx. 2.0 VA (1.6 W) * 24 to 48 VAC/12 to 48 VDC (When at 24 VDC) Relay ON: approx. 0.8 W H3CR-AP (see note 3) * 100 to 240 VAC/100 to 125 VDC (When at 240 VAC, 60 Hz) Relay ON: approx. 2.5 VA (2.2 W) * 24 to 48 VAC/12 to 48 VDC (When at 24 VDC) Relay ON: approx. 0.9 W H3CR-A8E * 100 to 240 VAC/100 to 125 VDC (When at 240 VAC, 60 Hz) Relay ON/OFF: approx. 2 VA (0.9 W) * 24 to 48 VAC/VDC (When at 24 VDC) Relay ON/OFF: approx. 0.9 W H3CR-AS/-A8S * 24 to 48 VAC/12 to 48 VDC (When at 24 VDC) Output ON: 0.3 W Output OFF: 0.2 W Time limit contacts: Transistor output: Instantaneous contact:
Power consumption
Relay OFF: approx. 1.3 VA (1.1 W) Relay OFF: approx. 0.2 W
Relay OFF: approx. 1.8 VA (1.7 W) Relay OFF: approx. 0.3 W
Control outputs
5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos = 1) Open collector (NPN/PNP), 100 mA max. at 30 VDC max., residual voltage: 2 V max. 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos = 1)
Note: 1. DC ripple rate: 20% max. if the power supply incorporates a single-phase, full-wave rectifier. 2. Each 24-to-48-VAC/12-to-48-VDC model causes an inrush current of approximately 0.85 A. Pay careful attention when attempting to turn ON power to such a model with non-contact output from a device such as a sensor. 3. The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the input circuit.
B-112
Solid-state Multi-functional Timer H3CR-A
I Characteristics
Accuracy of operating 0.2% FS max. (0.2%10 ms max. in a range of 1.2 s) time Setting error Reset time Reset voltage Influence of voltage Influence of temperature Insulation resistance Dielectric strength 5% FS 50 ms (see note 1) Min. power-opening time: 0.1 s max. Min. pulse width: 0.05 s (H3CR-A/-AS) 10% max. of rated supply voltage 0.2% FS max. (0.2%10 ms max. in a range of 1.2 s) 1% FS max. (1%10 ms max. in a range of 1.2 s) 100 M min. (at 500 VDC) 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed noncurrent-carrying metal parts) 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) 2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP 3 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC 4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to 125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC 1.5 kV (between power terminals) and 600 V (between no-voltage input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 s, 1-ns rise) Malfunction: 8 kV Destruction: 15 kV Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each Destruction: 1,000 m/s2 3 times each in 6 directions Malfunction: 100 m/s2 3 times each in 6 directions Operating: Storage: Operating: -10C to 55C (with no icing) -25C to 65C (with no icing) 35% to 85% Timers
Impulse withstand voltage Noise immunity Static immunity Vibration resistance Shock resistance Ambient temperature Ambient humidity Life expectancy EMC
Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (see note 2) (EMI) Emission Enclosure: Emission AC Mains: (EMS) Immunity ESD: EN61812-1 EN55011 Group 1 class A EN55011 Group 1 class A EN61812-1 IEC61000-4-2: 6 kV contact discharge (level 3) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: IEC61000-4-3:10 V/m (80 MHz to 1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves:IEC61000-4-3:10 V/m (9005 MHz) (level 3) Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4) Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3) 2 kV line to ground (level 3) Light gray (Munsell 5Y7/1) IP40 (panel surface) Approx. 90 g
Case color Degree of protection Weight
Note: 1. The value is 5% FS +100 ms to -0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF. 2. Refer to the Life-test Curve.
Solid-state Multi-functional Timer
H3CR-A
B-113
I Life-test Curve
10,000
Switching operations (x 103)
5,000
1,000 500 30 VDC L/R = 7 ms 250 VAC/30 VDC (cos = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cos = 1) and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA (100 mA for H3CR-A8E) at 5 VDC (failure level: P).
100 250 VAC (cos = 0.4)
Load current (A)
B-114
Solid-state Multi-functional Timer H3CR-A
Connections
H3CR-A/AS
AC (DC) input Zero setting detection circuit Time range/ unit selectors Operating mode selector
Timers
I Block Diagrams
Power supply circuit
Oscillation circuit
Counting circuit
Output circuit
Reset input, start input, and gate input
Input circuit
Indicator circuit
Power-ON Output-ON indicator indicator
H3CR-AP
AC (DC) input Zero setting detection circuit Time range/ unit selectors Operating mode selector
Power supply circuit
Oscillation circuit
Counting circuit
Output circuit
Start
Input circuit
Indicator circuit
Power-ON Output-ON indicator indicator
Solid-state Multi-functional Timer
H3CR-A
B-115
H3CR-A8/A8S
AC (DC) input Zero setting detection circuit Time range/ unit selectors Operating mode selector
Power supply circuit
Oscillation circuit
Counting circuit
Output circuit
Indicator circuit
Power-ON Output-ON indicator indicator
H3CR-A8E
AC (DC) input Zero setting detection circuit Time range/ unit selectors Operating mode selector
Power supply circuit
Oscillation circuit
Counting circuit
Output circuit
Indicator circuit
Power-ON Output-ON indicator indicator Instantaneous output circuit
I I/O Functions
Inputs (for -A/ Start -AS models) Reset Gate Outputs Control output Starts time-measurement. Interrupts time-measurement and resets time-measurement value. No time-measurement is made and control output is OFF while the reset input is ON. Prohibits time-measurement. Outputs are turned ON according to designated output mode when preset value is reached.
Note: H3CR-AP incorporates start input only.
B-116
Solid-state Multi-functional Timer H3CR-A
I Terminal Arrangement
Note: The delayed contact of conventional Timers was indicated as Timers The contact symbol of the H3CR-A is indicated as because its operating mode is six multi-modes (four multi-modes for the H3CR-A8).
11-pin Models
H3CR-A/-A-300/-A-301 (Contact Output)
8-pin Models
H3CR-A8/-A8-301 (Contact Output)
Reset input
Gate input
Start input
Power supply Power supply
H3CR-A8S (Transistor Output)
H3CR-AS (Transistor Output)
Reset input
Gate input
Start input
Power supply
Note: Terminals 1, 3, 4, and 5 are empty. Terminals 2 and 7 are the same as for the H3CR-A8.
H3CR-A8E (Contact Output)
Power supply
Note: Terminals 1, 3, 4, and 8 are empty. Terminals 2, 5, 6, 7, and 10 are the same as for the H3CR-A.
H3CR-AP (Contact Output)
Start input
Power supply
Power supply
Note: Terminal 5 is empty.
Solid-state Multi-functional Timer
H3CR-A
B-117
I Input Connections
H3CR-A/-AS
The inputs of the H3CR-A/-AS are no-voltage (short-circuit or open) inputs.
No-voltage Inputs
No-contact Input (Connection to NPN open collector output sensor.)
12 to 24 VDC (sensor power supply) + DC power - supply Timer Timer
Contact Input
No-contact Input (Connection to a voltage output sensor.)
12 to 24 VDC (sensor power supply) + DC power - supply Timer
Sensor
Sensor
5 Gate 6 Start 7 Reset 2 Input (0 V) 5 Gate 6 Start 7 Reset 2 Input (0 V) 5 Gate 6 Start 7 Reset 2 Input (0 V)
Operates with transistor ON
Operates with relay ON
Operates with transistor ON
No-voltage Input Signal Levels No-contact input 1. Short-circuit level Transistor ON Residual voltage: 1 V max. Impedance when ON: 1 k max. 2. Open level Transistor OFF Impedance when OFF: 100 k min. Contact input Use contacts which can adequately switch 0.1 mA at 5 V
B-118
Solid-state Multi-functional Timer H3CR-A
H3CR-AP
The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Voltage Inputs
No-contact Input (Connection to PNP open collector output sensor)
12 to 24 VDC (sensor power supply) Sensor + DC power - supply Timer 10 Power supply (+) 6 Start 7 2 Input 0V Power supply (-)
No-contact Input (Connection to NPN open collector output sensor)
12 to 24 VDC (sensor power supply) Sensor + DC power - supply Timer
Contact Input
10 Power supply (+) 6 Start 7 2 Input 0V Power supply (-)
DC power supply
AC power supply
Timer 10 Power supply (+) 6 Start 7 2 Input 0V Power supply (-)
Operates with PNP transistor ON
Operates with NPN transistor ON
Operates with relay ON
Note: The input circuit is isolated from the power supply circuit. Thus, an NPN transistor can be connected. Voltage Input Signal Levels No-contact input 1. Transistor ON Residual voltage: 1 V max. The voltage between terminals 6 and 7 must be 10.8 VDC min. 2. Transistor OFF Leakage current: 0.01 mA max. The voltage between terminals 6 and 7 must be 1.2 VDC max. Contact input Use contacts that can adequately switch 0.1 mA at each operating voltage. The voltage between terminals 6 and 7 with contacts ON or OFF must satisfy the specified value. Contacts ON 100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC or 85 to 137.5 VDC 24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or 10.8 to 52.8 VDC Contacts OFF 100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or 0 to 10 VDC 24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to 1.2 VDC
Note: Refer to the signal levels in the following table and be aware of the minimum applicable load of the relay.
Solid-state Multi-functional Timer
H3CR-A
B-119
Timers
Operation
I Timing Chart
Note: 1. 2. 3. 4. The minimum power-opening time ("Rt") is 0.1 s. The minimum input pulse width (for start, reset) is 0.05 s. The letter "t" in the timing charts stands for the set time and "t-a" means that the period is less than the time set. Power supply start in mode J is also possible for H3CR-A8/-A8E/-A8S/-A8-301 models.
H3CR-A/-AS/-AP*
*H3CR-AP model incorporates start input only. Operating mode A: ON-delay
Power Start Reset Output relay (NC) Output relay (NO) (Output indicator) Power indicator Power Start (see note) Output t t
Timing chart
Basic operation
t
Note: Start input is invalid while the Timer is in operation.
Basic operation
B: Flicker OFF start
Power Start Reset Output relay (NC) Output relay (NO) (Output indicator) Power indicator Output Power Start (see note)
t
t
t
t
Note: Start input is invalid while the Timer is in operation.
Basic operation
B2: Flicker ON start
Power Power Start Reset Output relay (NC) Output relay (NO) (Output indicator) Power indicator Start (see note) Output
t
t
t
t
Note: Start input is invalid while the Timer is in operation.
Basic operation
C: Signal ON/ OFFdelay
Power Start Reset Output relay (NC) Output relay (NO) (Output indicator) Power indicator
Power
Start (see note) Output
t
t
t
t
Note: Start input is valid and retriggerable while the Timer is in operation.
B-120
Solid-state Multi-functional Timer H3CR-A
Operating mode D: Signal OFFdelay
Power Start Reset Output relay (NC)
Timing chart
Basic operation
Power Start (see note) Output Output relay (NO) (Output indicator) Power indicator
t
Note: Start input is valid and re-triggerable while the Timer is in operation.
Basic operation
E: Interval
Power Start Reset Output relay (NC) Output relay (NO) (Output indicator) Power indicator
Power Start (see note) Output
t
Note: Start input is valid and re-triggerable while the Timer is in operation.
Basic operation
G: Signal ON/ OFFdelay
Power Start Reset Output relay (NC) Output relay (NO) (Output indicator) Power indicator Output Power Start (see note)
t
t
t
t
Note: Start input is valid and re-triggerable while the Timer is in operation.
Basic operation
J: One-shot output
Power Start Reset Output relay (NC) Output relay (NO) (Output indicator) Power indicator 10.6 s (Fixed) 10.6 s (Fixed) Output Power Start (see note)
t
10.6 s (Fixed)
Note: Start input is valid and retriggerable while the Timer is in operation.
Gate Signal Input
t1 ON Power OFF Start ON OFF Gate ON OFF Reset ON OFF Output ON relay OFF t2
Note: 1. This timing chart indicates the gate input in operating mode A (ON-delay operation). 2. The set time is the sum of t1 and t2. 3. H3CR-AP model incorporates start input only.
Solid-state Multi-functional Timer
H3CR-A
B-121
Timers
H3CR-A8/-A8S
Operating mode A: ON-delay
Power Output relay (NC) Output relay (NO) (output indicator) Power indicator
Timing chart
Basic operation
Power t Output
B2: Flicker ON start
Power Output relay (NC) Output relay (NO) (output indicator) Power indicator
Basic operation
Power t Output t t t
E: Interval
Power Output relay (NC) Output relay (NO) (output indicator) Power indicator
Basic operation
Power t Output
J: One-shot output
Power
Output relay (NC) Output relay (NO) (output indicator) Power indicator 10.6 s (Fixed) 10.6 s (Fixed)
Basic operation
Power t Output
10.6 s (Fixed)
Note: 1. The minimum power-opening time ("Rt") is 0.1 s. 2. The letter "t" in the timing charts stands for the set time and "t-a" means that the period is less than the time set.
B-122
Solid-state Multi-functional Timer H3CR-A
H3CR-A8E
Operating mode A: ON-delay
Power Output relay (NC) Output relay (NO) (output indicator) Instantaneous output relay (NC) Instantaneous output relay (NO) Power indicator
Timing chart Timers
Basic operation
Power t Output
B2: Flicker ON start
Power Output relay (NC) Output relay (NO) (output indicator) Instantaneous output relay (NC) Instantaneous output relay (NO) Power indicator
Basic operation
Power t Output t t t
E: Interval
Power Output relay (NC) Output relay (NO) (output indicator) Instantaneous output relay (NC) Instantaneous output relay (NO) Output Power indicator
Basic operation
Power t
J: One-shot output
Power Output relay (NC) Output relay (NO) (output indicator) Instantaneous output relay (NC) Instantaneous output relay (NO) Output Power indicator (Fixed) (Fixed)
Basic operation
Power t 10.6 s (Fixed)
Note: 1. The minimum power-opening time ("Rt") is 0.1 s. 2. The letter "t" in the timing charts stands for the set time and "t-a" means that the period is less than the time set.
Solid-state Multi-functional Timer
H3CR-A
B-123
Nomenclature
Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating) Operating mode display window Output indicator (orange) (Lit when output) Operating mode selector Select a mode from: A, B, B2, C, D, and E (H3CR-A, -AP, and -AS) A, B2, E and J (H3CR-A8, -A8S, and -A8E) G and J (H3CR-A-300) Scale range display windows Time range selector (select one from 1.2, 3, 12, and 30 at full scale; with the H3CR-A@-301, select from 2.4, 6, 24, or 60 at full scale. ) Time unit display window Time unit selector (select one from sec, min, hrs, and 10h)
Time setting knob (set time)
B-124
Solid-state Multi-functional Timer H3CR-A
Dimensions
Note: All units are in millimeters unless otherwise indicated.
H3CR-A H3CR-AP H3CR-AS
48
15 6
66.6 52.3 0.7
48
39 dia.
44.8 x 44.8
11 pins
H3CR-A8 H3CR-A8S H3CR-A8E
48
15 6
66.6 52.3 0.7
48
39 dia.
44.8 x 44.8
8 pins
Dimensions with Set Ring
50
16.5
50
42 dia.
Time Setting Ring
Panel cover
Dimensions with Front Connecting Socket P2CF-08-@/P2CF-11-@
Dimensions with Back Connecting Socket P3G-08/P3GA-11
15 81.5 80 15 81.5 75
100.8*
H3CR-A H3CR-AS H3CR-AP
H3CR-A8@ 98.5 89.9* 87.6 H3CR-A H3CR-AS H3CR-AP + Adapter H3CR-A8@ + Adapter
Y92F-30 P2CF-11 P2CF-11-E
2.3*
P2CF-08 P2CF-08-E
2.3*
P3GA-11 (When Y92A-48G mounted)
Y92F-30
P3G-08 (When Y92A-48G mounted)
*These dimensions vary with the kind of DIN track (reference value).
Solid-state Multi-functional Timer
H3CR-A
B-125
Timers
Application Examples (H3CR-A)
A Mode: ON-delay
ON-delay operation (A mode) is a basic mode.
1. Power-ON Start/Power-OFF Reset
The Power-ON start/Power-OFF reset operation is a standard operating method.
t
3. Control of Integrated Time with Gate Signal
With a gate signal, the Power-ON start operation and Signal start operation can be controlled (the operation can be interrupted).
t1 Power (2 and 10) Start (2 and 6) Gate (2 and 5) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) t2 t1 + t2: set time
Power (2 and 10) Start (2 and 6) Reset (2 and 7) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power indicator Flashing Externally short-circuited Lit
Power indicator Flashing Lit Gate signal (The operation is interrupted with the gate signal if the Timer detects an abnormal signal.)
Externally short-circuited
Power supply
2. Signal Start/Signal Reset
The Signal start/Signal reset operation is useful for remote control of the Timer.
Power supply
B/B2 Mode: Flicker
The flicker operation in the B and B2 modes can be effectively applied to lamp or buzzer (ON and OFF) alarms or the monitoring of an intermittent operation with a display.
Power (2 and 10) Start (2 and 6) Reset (2 and 7) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power indicator Lit Flashing Lit
1. Power-ON Start/Power-OFF Reset (in B Mode)
Power (2 and 10) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power indicator
Start signal (remote control possible) Reset signal (remote control possible)
Flashing
Externally short-circuited
Power supply (Power continuously supplied)
Power supply
B-126
Solid-state Multi-functional Timer H3CR-A
2. Signal Start/Signal Reset (in B Mode)
If there is an abnormal signal, flashing starts. When the abnormal condition is restored, a reset signal stops the display flashing.
t t
2. Signal-ON-OFF Start/Instantaneous Operation/Time-limit Reset
Power (2 and 10) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power indicator
Lit Lit Lit Flashing Flashing Flashing Lit
Power (2 and 10) Start (2 and 6) Reset (2 and 7) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power indicator Lit Start signal Reset signal Flashing Lit
Start signal (The operation starts with the signal ON or OFF)
Power supply Power supply (Power continuously supplied)
(Power continuously supplied)
C Mode: Signal ON/OFF-delay
The Signal ON-/OFF-delay operation (C mode) is useful for the control of distribution of products on a production line into boxes by the specified number or time.
D Mode: Signal OFF-delay
Signal OFF-delay operation (D mode) can be effectively used to keep a load operating for a certain period. For example, this function enables the cooling fan for a lamp or heater to operate for a certain period after the lamp or heater is switched OFF.
1. Power-ON Start/Instantaneous Operation/ Time-limit Reset
A set of these functions is useful for the operation of a machine for a specified period when power is ON.
1. Power-ON Start/Instantaneous Operation/ Time-limit Reset
Power (2 and 10) Start (2 and 6)
Power (2 and 10) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3)
Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power indicator Lit Flashing Lit
Externally short-circuited
Start signal (NC to NO)
Power supply
Power supply
Solid-state Multi-functional Timer
H3CR-A
B-127
Timers
2. Signal Start/Instantaneous Operation/ Time-limit Reset
Power (2 and 10) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) Power indicator Lit Flashing Lit
2. Signal Start/Instantaneous Operation/ Time-limit Reset
This function is useful for the repetitive control such as the filling of liquid for a specified period after each Signal start input.
t Power (2 and 10) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3) t
Start signal (NO to NC to NO)
Start signal
Power supply
(Power continuously supplied)
Power supply
(Power continuously supplied)
E Mode: Interval
1. Power-ON Start/Instantaneous Operation/ Time-limit Reset
This function is useful for the operation of a machine for a specified period after power is ON.
Power (2 and 10) Start (2 and 6) Control output: NC (8 and 11) NC (1 and 4) Control output: NO (9 and 11) NO (1 and 3)
Externally short-circuited
Power supply
B-128
Solid-state Multi-functional Timer H3CR-A
Precautions (H3CR-A)
Note: The undermentioned is common for all H3CR-A models.
I Power Supplies
For the power supply of an input device of the H3CR-A@/-A@S/-AP , use an isolating transformer with the primary and secondary windings mutually isolated and the secondary winding not grounded. Example: H3CR-A
H3CR-A G, S, R 5, 6, 7 Input terminal 2 10 2 Power supply
I Input/Output
Relationship between Input and Power Supply Circuits (except for H3CR-A8E)
The H3CR-A (except for H3CR-A8E) uses transformerless power supply. When connecting a relay or transistor as an external signal input device, pay attention to the following points to prevent short-circuiting due to a sneak current to the transformerless power supply. If a relay or transistor is connected to two or more Timers, the input terminals of those Timers must be wired properly so that they will not differ in phase, otherwise the terminals will be short-circuited to one another.
Incorrect
Contact or transistor for external input signal Input device Isolation transformer is required.
Short-circuit current H3CR-A
The H3CR-A@/-A@S/AP's power supply terminal 2 is a common terminal for input signals to the Timer. Do not disconnect the wires on terminal 2, otherwise the internal circuitry of the Timer will be damaged.
Input terminal
Power supply
Input terminal 5, 6, 7 G, S, R Input terminal H3CR-A
10
Correct
Input terminal
2
Power supply
Make sure that the voltage is applied within the specified range, otherwise the internal elements of the Timer may be damaged.
Input terminal
It is impossible to provide two independent power switches as shown below regardless of whether or not the Timers are different in phase.
Input terminal
Power supply
Input terminal
Solid-state Multi-functional Timer
H3CR-A
B-129
Timers
Relationship between Input and Power Supply Circuits (H3CR-A@/-A@S)
An appropriate input is applied to the input signal terminals of the H3CR-A@/-A@S when one of the input terminals is short-circuited with the common terminal (terminal 2) for the input signals. Never use terminal 10 as the common terminal for this purpose, otherwise the internal circuit of the Timer will be damaged.
If a relay or transistor is connected to two or more Timers, the input terminals of those Timers must be wired properly so that they will not be different in phase or the terminals will be short-circuited to one another (refer to the figures below).
Incorrect
Contact or transistor for external input signal 10 6 H3CR-AP 7 Power supply
Incorrect
10
2 H3CR-A 5, 6, 7 G, S, R Input terminal 2 6 H3CR-AP Short-circuit current 10
AC or DC power supply
7
Correct
5, 6, 7 G, S, R Input terminal AC or DC power supply 10
2
Correct
Contact or transistor for external input signal 10 6
H3CR-A
2 7
H3CR-AP
Power supply
2
Do not connect a relay or any other load between input terminals, otherwise the internal circuit of the Timer will be damaged due to the high-tension voltage applied to the input terminals.
10 6 10 Ry AC or DC power supply Input contact H3CR-A 7 H3CR-AP
Short-circuit current
5, 6, 7 G, S, R Input terminal
2
2
Common to All H3CR-A Models
With the H3CR-AP input wires must be as short as possible. If the , floating capacity of wires exceeds 1,200 pF (approx. 10 m for cables with 120 pF/m), the operation will be affected. Pay particular attention when using shielded cables. The H3CR-A@S transistor output is isolated from the internal circuitry by a photocoupler. Therefore, either NPN or PNP output is possible.
Relationship between Input and Power Supply Circuits (H3CR-AP)
H3CR-AP AC/DC power supply
Input circuit
Power supply circuit
Since the input circuit and the power supply circuit are configured independently, the input circuit can be turned ON or OFF irrespective of the ON/OFF state of the power supply. It must be noted that a voltage equivalent to the power supply voltage is applied to the input circuit.
B-130
Solid-state Multi-functional Timer H3CR-A


▲Up To Search▲   

 
Price & Availability of H3CR-AP-300

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X